FM Approval |
|
 |
|
|
|
|
|
Fab-Tech, Inc's
Model PermaShield Pipe fume and/or smoke exhaust duct materials
(circular stainless steel duct interiorly coated with an
electrostatically applied fluoropolymer resin) are FMRC approved
up to a maximum 60 inch (1524mm) diameter when manufactured in
accordance with S.M.A.C.N.A. Round Industrial Duct Construction
Standards. |
|
 |
|
|
|
|
|
Limitations
& Requirements: |
|
 |
|
|
|
|
|
1. |
All ducts shall be
interiorly furnished with a fluoropolymer resin coating
consisting of a prime coat 2 to 3 mil (0.05-0.07mm) thick and a
top coat 7 to 8 mil (0.18-0.20mm) thick. The total
interior coating thickness shall not exceed an average of 10 mil
(0.25mm). |
|
 |
|
|
|
|
|
2. |
This duct may be
used for smoke removal in special purpose areas when properly
designed and sized. Sprinklers are not required. |
|
 |
|
|
|
|
|
3. |
The product shall
be manufactured with identical resins as tested, and according
to the formulation on file with FMRC, and shall meet all
physical requirements of S.M.A.C.N.A. manual for Industrial Duct
Construction Standards. |
|
 |
|
|
|
|
|
4. |
Vertical height of
individual risers within the duct system are not restricted,
however, they shall not penetrate other fire areas. |
|
 |
|
|
|
|
|
5. |
The manufacturer
shall determine the suitability of the duct system for specific
corrosive environments. |
|
 |
|
|
|
|
|
6. |
If the process
served by such duct system produces flammable residue or a
combustible fume source exceeding 1 square foot (0.09m) in area
per inlet which can build up inside the duct, then internal
sprinklers will be required. |
|
 |
|
|
|
|
|
7. |
The ASTME 84
Standard Test Method for Surface Burning Characteristics.
Tested in flat sheet form at a 20 ga. (0.95mm) thickness:
Flame Spread 10, Smoke Density 15. |
|
 |
|
|
|
|
|
|
Caution:
These numerical flame spread and smoke density values do not
define the hazards presented by this of any other material under
actual fire conditions. |
|
 |
|
|
|
|